Trigeneration and Quadgeneration: Terms and Definitions
This section contains terms and definitions for trigeneration and quadgeneration – technologies that extend cogeneration by adding the production of cooling and CO2. Compiled by the engineers of KTS Engineering, the official INNIO Jenbacher distributor in Ukraine.
Trigeneration (CCHP)
- Trigeneration
Trigeneration - a technology for the simultaneous production of electricity, heat and cooling from a single fuel source. The gas engine generates electricity; the engine's heat (from the cooling jacket and exhaust gases) is fed to an absorption chiller, which produces chilled water (6-12°C) for air conditioning or process cooling. Unlike simple cogeneration, trigeneration makes productive use of engine heat even in summer, when there is no heating demand. The overall efficiency of a trigeneration system is 80-90%.
Synonyms: CCHP · combined cooling, heat and power · trigeneration system
- CCHP
CCHP (Combined Cooling, Heat and Power) - the international designation for trigeneration: a system for the combined production of cooling, heat and electricity. It is used in INNIO technical documentation and international engineering standards. It differs from CHP (cogeneration) by the addition of a cooling circuit based on an absorption chiller. KTS Engineering designs CCHP plants for facilities with a year-round air conditioning demand.
Synonym: trigeneration
- Trigeneration Plant
Trigeneration plant - an energy system comprising a Jenbacher gas engine, a synchronous generator, a heat recovery system and an absorption chiller. The plant is connected to the gas pipeline, the company's electrical network, the heating system and the chilled water or air conditioning system. KTS Engineering provides the full cycle: design, supply, installation and service of turnkey trigeneration plants.
Synonyms: CCHP system · trigeneration complex
- Trigeneration for Shopping Malls and Business Centers
Trigeneration for shopping malls and business centers - the use of CCHP at large commercial real estate facilities with a high and continuous air conditioning load. In winter, engine heat is used for space heating; in summer, it goes to an absorption chiller to produce cooling. Electricity and HVAC costs are reduced by 30-50%. An added benefit is backup power during grid outages.
- Trigeneration for the Food Industry
Trigeneration for the food industry - the use of CCHP at plants that need both process heat (cooking, pasteurization, sterilization) and process cooling (storage, product chilling). The gas engine supplies electricity; exhaust heat is fed via a heat recovery boiler into the steam system, and cooling jacket heat goes to an absorption chiller. Documented KTS Engineering case: energy costs cut by 51% for a soft drinks producer.
- Trigeneration for Data Centers
Trigeneration for data centers - the use of CCHP at facilities with a high and stable year-round cooling load for server equipment. A data center needs cooling constantly, which makes an absorption chiller cost-effective at any time of year. KTS Engineering also provides backup power in the form of island operation if the external grid fails.
- Turnkey Trigeneration
Turnkey trigeneration - the complete range of KTS Engineering services for creating a trigeneration facility: feasibility study, equipment selection and supply (Jenbacher + absorption chiller), construction and installation works, commissioning, staff training and long-term service. The customer receives a working system for power, heating and cooling supply.
Absorption Chillers and Equipment
- Absorption Refrigeration Machine (Absorption Chiller)
Absorption refrigeration machine (absorption chiller) - a refrigeration unit driven by thermal energy rather than an electric compressor. In trigeneration systems, the absorption chiller uses heat from the exhaust gases or engine coolant of a gas engine to drive a thermochemical cycle. The working fluid is a lithium bromide solution (LiBr/H2O) or an ammonia/water pair. The output is chilled water at 6-12°C supplied to the air conditioning or process cooling system.
Synonyms: absorption chiller · heat-driven chiller · waste heat chiller
- Absorption Chiller
Absorption chiller - the common name for an absorption refrigeration machine in design and commercial documentation. A chiller is a refrigeration machine that produces chilled water. Unlike an electrically driven vapor-compression chiller, an absorption chiller consumes thermal energy, which makes it an indispensable component of trigeneration systems.
Synonym: absorption refrigeration machine
- Lithium Bromide Absorption Chiller
Lithium bromide absorption chiller - the most common type of absorption chiller in trigeneration systems. Its working pair is lithium bromide (LiBr) as the absorbent and water as the refrigerant. It produces chilled water at 6-12°C. It is driven by heat at 80-130°C from the engine coolant or from exhaust gases via a heat recovery boiler. It is characterized by low power consumption: only pumps and fans.
- Cooling Capacity (kW / Gcal/h)
Cooling capacity - the heat output that an absorption chiller can remove from the medium being cooled per unit of time. It is measured in kW or Gcal/h. It depends on the temperature of the hot water supplied, the cooling water temperature and the required chilled water outlet temperature. KTS Engineering engineers select an absorption chiller to match a specific Jenbacher engine at the design stage.
- COP (Coefficient of Performance)
COP (Coefficient of Performance) - the ratio of an absorption chiller's cooling capacity to the thermal energy it consumes. For single-effect lithium bromide machines, COP = 0.6-0.8; for double-effect machines, 1.0-1.4. A value below one means that 1.2-1.6 kW of heat is used to produce 1 kW of cooling - which still pays off, because in trigeneration the heat is a by-product of the engine.
- Chilled Water (Secondary Coolant)
Chilled water (secondary coolant) - the fluid that carries cooling from the absorption chiller to the consumers: fan coil units, the ventilation system and process equipment. As a rule, it is water at 6-12°C. For systems with temperatures below 0°C, an aqueous solution of ethylene glycol or propylene glycol is used.
- Heat Recovery Boiler (HRSG)
Heat recovery boiler (HRSG - Heat Recovery Steam Generator) - a heat exchanger in the exhaust gas path of a gas engine or turbine. It recovers exhaust heat (400-550°C) to produce hot water or steam. In trigeneration systems, the hot water or steam from the heat recovery boiler is fed to an absorption chiller. The heat recovery boiler is part of the standard scope of a Jenbacher cogeneration system.
Synonyms: HRSG · waste heat boiler · exhaust gas heat exchanger
Quadgeneration
- Quadgeneration
Quadgeneration - a technology for producing four outputs from a single fuel source: electricity, heat, cooling and carbon dioxide (CO2). The CO2 contained in the exhaust gases of a Jenbacher gas engine (3-4%) is captured in a dedicated CO2 capture unit, purified and fed under pressure into greenhouses. A higher CO2 concentration speeds up photosynthesis and plant growth by 20-30%. KTS Engineering designs quadgeneration solutions for greenhouse complexes in Ukraine.
Synonyms: quadrigeneration · four-output system · cogeneration with CO2 capture
- Quadrigeneration
Quadrigeneration - an alternative spelling of quadgeneration found in some technical literature and regulatory documents. Both spellings refer to the same technology - producing four useful outputs (electricity, heat, cooling, CO2) from a single fuel source.
Synonym: quadgeneration
- CO2 for Greenhouses
CO2 for greenhouses - carbon dioxide added to greenhouse air to stimulate plant photosynthesis. The optimal CO2 concentration in a greenhouse is 800-1,200 ppm, compared with 400 ppm in ambient air. In quadgeneration systems, the CO2 source is the purified exhaust gas of a Jenbacher engine. Savings on purchased commercial CO2 further improve the economics of the greenhouse complex.
Related terms: quadgeneration · CO2 capture unit
- CO2 Capture Unit (Carbon Capture Unit)
CO2 capture unit (Carbon Capture Unit) - a dedicated unit that extracts CO2 from engine exhaust gases and prepares it for supply to a greenhouse. The process includes cooling the exhaust gases, removing NOx and SOx, absorbing CO2 in an amine solvent, desorbing it to obtain pure CO2 and compressing it to working pressure. The CO2 purity is at least 99.5%. In a quadgeneration complex, the unit is integrated into the overall system downstream of the heat recovery boiler.
Synonyms: CO2 scrubber · CO2 recovery unit
- Quadgeneration for Greenhouse Complexes
Quadgeneration for greenhouse complexes - the use of quadgeneration to supply a greenhouse with electricity, heat for space heating, cooling when needed in summer and CO2 for enriching the atmosphere. The system's synergy: one cubic meter of gas burned yields four useful outputs. It is most cost-effective for year-round greenhouse complexes with supplemental electric lighting.
Related terms: CO2 for greenhouses · CO2 capture unit
Trigeneration (CCHP - Combined Cooling, Heat and Power) is the simultaneous production of electricity, heat and cooling from a single fuel source. The engine's heat is fed to an absorption chiller, which produces cooling for air conditioning or process cooling. The overall efficiency of a trigeneration system is 80-90%.
Cogeneration produces two outputs: electricity and heat. Trigeneration adds a third - cooling, produced in an absorption chiller using engine heat. Trigeneration pays off best at facilities with a year-round air conditioning load: in summer, heat that would go unused in cogeneration is turned into cooling.
Quadgeneration is the production of four outputs from a single fuel source: electricity, heat, cooling and carbon dioxide (CO2). CO2 from the exhaust gases of a Jenbacher engine is captured, purified and fed into greenhouses, accelerating plant growth by 20-30%.