Cogeneration Plant Engineering Systems: Terms and Definitions

This section contains terms and definitions for the engineering systems of cogeneration plants: the thermal section, the electrical section and automation systems. KTS Engineering designs, installs and services all engineering systems of cogeneration facilities on a turnkey basis.

Thermal Section and Heat Recovery

Heat Recovery Boiler (HRSG)

Heat recovery boiler (HRSG - Heat Recovery Steam Generator) - a heat exchanger installed in the exhaust gas path of a gas engine to recover exhaust heat and produce hot water or process steam. Jenbacher exhaust gases have a temperature of 390-450°C and carry 40-50% of the engine's thermal output. The heat recovery boiler transfers this heat to the heating system or to an absorption chiller. It is an essential element of a cogeneration plant with full heat recovery.

Synonyms: HRSG · waste heat boiler · exhaust gas economizer

Heat Exchanger (Plate / Shell-and-Tube)

Heat exchanger - a device that transfers thermal energy from one fluid to another without mixing them. Cogeneration plants use:

  • Plate heat exchangers - very compact with intensive heat transfer; used for engine cooling (HT/LT circuits) and for transferring heat to the consumer;
  • Shell-and-tube heat exchangers - reliable at high pressure and temperature; used in high-temperature circuits and steam systems.

Heat exchangers are part of the scope of supply of a Jenbacher cogeneration plant.

Hot Water Buffer Tank

Hot water buffer tank - an insulated tank for storing hot water that balances the mismatch between the heat output of a cogeneration plant (constant) and the company's heat consumption (variable). When there is excess heat, the buffer tank is charged; when there is a shortfall, it releases the stored heat to the consumer. Buffer tank volumes range from a few m³ to several hundred m³ depending on the daily consumption profile.

Synonyms: heat accumulator · buffer vessel · thermal storage tank

Peak-Load (Backup) Boiler

Peak-load boiler (backup boiler) - a gas-fired or electric boiler that is switched on to cover peak heat demand exceeding the output of the cogeneration plant, and to back up the heat supply during scheduled maintenance or an emergency shutdown of the genset. The peak-load boiler is sized to provide 100% backup of the company's heat supply.

Process Steam

Process steam - steam used directly in a company's production processes: sterilization, pasteurization, heating, evaporation and equipment heating. A cogeneration plant with a heat recovery boiler can produce saturated steam at up to 10 bar (180°C). Higher steam pressures require a gas turbine or a separate steam boiler.

HT/LT Heat Circuits

HT/LT heat circuits - the gas engine heat recovery system combining a high-temperature circuit (HT, 80-90°C) and a low-temperature circuit (LT, 40-60°C). The HT circuit cools the engine block and cylinder heads; its heat goes to the heating system or the heat recovery boiler. The LT circuit cools the intercooler and the oil; its heat can be used for domestic hot water or heating if needed. A correct HT/LT hydraulic layout is the key to maximum overall plant efficiency.

Related terms: HT and LT circuits of the engine

Heating Substation

Heating substation - the unit where heat from the cogeneration plant is transferred to the consumer's heating system or the district heating network. It includes heat exchangers, shut-off and control valves, circulation pumps and heat meters. With district heating, this is a building-level (individual) heating substation; with direct heat supply to the consumer, it is a heat distribution unit.

Hydraulic Separator

Hydraulic separator (low-loss header) - a hydraulic element of the thermal scheme that allows the primary circuit (engine - heat exchanger) and the secondary circuit (heat exchanger - consumer) to operate independently at different flow rates. It makes it possible to connect several heat consumers with different flow rates and temperatures without hydraulic conflicts. It is mandatory in schemes with several heat consumption circuits (space heating, domestic hot water, process steam).

Electrical Section

Power Transformer (Step-Up)

Power transformer (step-up) - an electrical machine that raises the generator output voltage (0.4 kV) to the voltage of the company's network (6, 10 or 35 kV) to reduce transmission losses. For large gensets (2 MW and above), the transformer is part of the cogeneration plant scope. The transformer rating is chosen equal to or slightly higher than the generator rating.

Switchgear / GIS

Switchgear (metal-enclosed switchgear) - a cabinet or set of cabinets with circuit breakers, disconnectors, instrument transformers and relay protection devices for distributing and controlling electricity. GIS (gas-insulated switchgear) - switchgear insulated with SF6 gas: more compact than air-insulated switchgear, used at high voltage (35 kV and above) or where space is limited. KTS Engineering supplies and installs switchgear as part of cogeneration facilities.

ATS (Automatic Transfer Switch)

ATS (automatic transfer switch) - a system that automatically transfers the power supply from the main source (the cogeneration plant) to the backup source (the centralized grid) when the main source trips or fails, and back again once it is restored. ATS transfer time ranges from fractions of a second (for static transfer switches) to several seconds (for conventional switching devices). KTS Engineering designs and installs ATS panels for all types of cogeneration facilities.

Synonyms: automatic transfer system · automatic transfer switch (ATS)

Relay Protection

Relay protection - a set of devices that automatically disconnect a faulty element of an electrical installation (generator, transformer, cable) in abnormal conditions: short circuits, overloads, unbalanced operation or loss of generator excitation. Mandatory for cogeneration plants: generator differential protection, reverse power protection (prevents the generator from motoring) and out-of-step protection.

Black Start

Black start - the ability of a power plant to start up and take load without an external power supply, using only its own sources (batteries for the control systems, self-contained engine start). This is an important feature for backup power plants and facilities operating in island mode. KTS Engineering implements the black start function for Jenbacher cogeneration plants at the customer's request.

Load Sharing

Load sharing - an algorithm that distributes active load evenly or proportionally between several generators running in parallel, or between gensets and the centralized grid. It is implemented in the PLC control system or directly in the DIA.NE controller. Load sharing is mandatory for modular power plants with several Jenbacher units.

Current Harmonics (THD)

Current harmonics (THD - Total Harmonic Distortion) - a measure of how far the current or voltage waveform deviates from an ideal sine wave. Non-linear loads (variable frequency drives, welding equipment, computers) generate current harmonics that overheat transformers and cables and cause interference in the network. For Leroy-Somer synchronous generators in gas engine gensets, voltage THD usually does not exceed 3-5% at rated load.

Automation and Control

Process Control System

Process control system (PCS) - a set of software and hardware for automating the control of a cogeneration plant and integrating it into the company's overall control system. It includes a unit-level PLC (engine control), a plant-level PLC or SCADA (control of the whole facility), an operator HMI and a supervisory dispatch system. KTS Engineering develops and implements process control systems for cogeneration facilities of any complexity.

PLC (Programmable Logic Controller)

PLC (Programmable Logic Controller) - an industrial microprocessor-based controller for automating processes. In cogeneration plants, the PLC controls auxiliary equipment: pumps, valves, cooling fans and the gas supply system. It communicates with the DIA.NE engine controller via Modbus or Profibus. Leading PLC platforms for power facilities: Siemens S7, Allen-Bradley, WAGO.

Synonyms: programmable controller · industrial controller

SCADA

SCADA (Supervisory Control And Data Acquisition) - a top-level supervisory control and data acquisition system. It shows the operator a mimic diagram of the facility with all parameters in real time, the event and alarm log, and parameter trends. It allows remote control of the equipment. For cogeneration facilities, KTS Engineering uses SCADA systems such as WinCC (Siemens), Ignition and others, depending on the customer's requirements. It can be integrated with the company's ERP system.

HMI (Human-Machine Interface)

HMI (Human-Machine Interface) - an operator panel with a touchscreen or buttons installed directly at the equipment. It shows the current status of the unit and its operating parameters and allows control operations to be performed. In Jenbacher cogeneration plants, the HMI is built into the unit's control panel; in addition, a plant-wide HMI with a mimic diagram of the entire system is installed. The DIA.NE controller has a built-in HMI screen.

ESD (Emergency Shutdown System)

ESD (Emergency Shutdown System) - a system for the automatic safe shutdown of a cogeneration plant in hazardous situations: gas in the engine room, fire, or critical parameter deviations (oil pressure, temperature, vibration). ESD is implemented on dedicated certified controllers (SIL 2-3 according to IEC 61511) separate from the main control system. KTS Engineering designs and installs ESD systems for cogeneration facilities.

Synonyms: ESD system · Emergency Shutdown · emergency protection system

EMS (Energy Management System)

EMS (Energy Management System) - a software suite for optimizing the operating modes of cogeneration plants and managing a company's electricity consumption. The EMS analyzes in real time the cogeneration plant's output, the company's consumption and the electricity and heat tariffs, and decides when to start or stop units, change load and buy or sell electricity to the grid in order to minimize costs.

Telemetry and Remote Dispatch

Telemetry and remote dispatch - systems for remote monitoring and control of cogeneration facilities. Data is transmitted via Ethernet, GSM/4G or satellite links. KTS Engineering runs its own dispatch system based on INNIO myPlant for continuous monitoring of the entire fleet of units it services. When an alarm event occurs, the system automatically notifies the KTS Engineering duty engineer.

Gas Detector (Gas Leak Sensor)

Gas detector (gas leak sensor) - a device for detecting leaks of combustible gas (methane) in a genset engine room or gas equipment room. When the gas concentration reaches 10-20% of the lower explosive limit (LEL), audible and visual alarms are activated, the solenoid valves on the gas line close automatically and emergency ventilation starts. It is a mandatory element of the safety system of a cogeneration facility.

Synonyms: gas leak detector · methane sensor · combustible gas alarm